Model SGK-12kV fully enclosed fully insulated ring main unit (hereinafter referred to as "gas insulated switchgear") is a new type of medium voltage ring main unit developed by our company by absorbing foreign advanced technology. The automatic laser cutting machine, NC sheet metal processing center, automatic welding machine, SF6 gas automatic maintenance equipment, various advanced testing instruments and supporting advanced flexible assembly production line are used to control the production and management of the company, which provides an effective guarantee for the high quality and reliability of switchgear. The ring main unit adopts modular design, with its perfect unification of fixed type and flexible expansion, which is suitable for different applications and provides satisfactory technical solutions for different users. The adoption of sensor technology and the latest microprocessor-based protection device, together with advanced technical performance, simple and flexible assembly scheme, can fully meet the changing needs of the market.
Model SKG-12KV fully enclosed fully insulated ring main unit suitable for 50HZ, 12KV power system, widely used in power supply terminal of industrial and civil cable ring network. Especially applicable to the following places: power distribution in urban residential areas, small secondary substations, switch stations, Industrial and mining enterprises, shopping malls, airports, subways, wind mills, medium and small power plants, hospitals, gymnasiums, railways, tunnels for protection and control of electric equipment.
Technical Parameters of SGK-12KV and SGK-24KV SF6 Gas Insulated Switchgears:
item
|
unit
|
panel C load
switch
|
panel F combined
electric apparatus
|
panel V vacuum
circuit breaker
|
panel V isolation/
earthing switch
|
|
rated voltage
|
KV
|
|
12(24)
|
|
|
1 min power frequency withstand voltage
|
|
|
|
|
|
|
phase-to-phase.
|
|
|
42/48(65/79)
|
|
rated
|
phase-to-earth1 isolation opening
|
|
|
|
|
|
insulation
|
lightning impulse withstand voltage
|
KV
|
|
|
|
|
level
|
phase to phase&phase to earth
|
|
|
75/85(125/145)
|
|
|
Across isolating opening
|
|
|
|
|
|
|
rated frequency
|
Hz
|
|
50
|
|
|
rated current
|
A
|
630
|
125
|
630/1250
|
630
|
rated short circuit open break current
|
KA
|
|
|
20/25/31.5
|
20/25
|
rated short time withstand current
|
KA
|
20
|
20/25
|
20/25/31.5
|
20/25
|
rated short circuit closing current(peak)
|
KA
|
|
|
63
|
80
|
|
rated peak withstand current
|
KA
|
50
|
50
|
63
|
80
|
rated earthing fault open break current
|
KA
|
17.3
|
21.7
|
21.7
|
17.3
|
rated short circuit duration time(main circuit)
|
S
|
|
4
|
|
|
rated operation sequence
|
|
|
O-0.3s-CO-180s-CO
|
|
mechanical life time(theoretical)
|
times
|
|
10000
|
|